Practical Example

https//www.racom.eu/eng/products/m/midge/app/hybnet/PracticalExample.html

Print version

1. Practical Example

UHF/VHF and Cellular network combination example

Fig. 1.1: UHF/VHF and Cellular network combination example

In the example, the SCADA Center is connected via RS232 interface to RipEX1 (COM1). The Center is utilized with Modbus RTU Master configuration and polls two RTUs connected via RipEX network. There is one distant RTU4 location which is reachable over the cellular network.

1.1. RipEX Center Configuration

RipEX Center Settings

Fig. 1.2: RipEX Center Settings

Apply the correct IP addresses within the Router mode and set the COM1 protocol.

Modbus Master configuration

Fig. 1.3: Modbus Master configuration

In the example, hexadecimal Modbus addresses 02 and 03 are transferred to the RipEX network on the Ethernet IP addresses. The Slave 04 is transferred via the cellular network and the destination IP address is the mobile IP address of the remote M!DGE unit. The COM port must be COM2 with UDP port 8882, otherwise the remote M!DGE would not handle the traffic correctly.

Central RipEX routing menu

Fig. 1.4: Central RipEX routing menu

In the Routing menu, three routes have to be added. First two are the LAN subnets of RipEX units and the third line defines the APN subnet (the gateway is the local M!DGE Ethernet IP address).

1.2. Remote RipEX Configuration

Both remote RipEX units have almost the same configuration so only R2 unit is described. Configure the correct IP addresses (together with RF frequency, …) and set the COM1 port as the Modbus Slave as in the following screenshot.

Remote RipEX Modbus Slave configuration

Fig. 1.5: Remote RipEX Modbus Slave configuration

The only missing configuration is the Routing rule to the central RipEX subnet (192.168.1.1/24).

Remote RipEX Routing menu

Fig. 1.6: Remote RipEX Routing menu

1.3. Central M!DGE Configuration

Central M!DGE Status menu

Fig. 1.7: Central M!DGE Status menu

The central M!DGE just needs to be configured so it is connected via the private APN, no other special configuration is needed.

1.4. Remote M!DGE Configuration

The remote M!DGE Status menu

Fig. 1.8: The remote M!DGE Status menu

After connecting to the private APN, only the Protocol server needs to be configured. In the INTERFACES – Serial Port, choose the Protocol server.

Serial Port configuration

Fig. 1.9: Serial Port configuration

Set the desired port settings.

Port settings

Fig. 1.10: Port settings

And as the last step, configure the Protocol server as the Modbus slave.

Modbus Slave M!DGE configuration

Fig. 1.11: Modbus Slave M!DGE configuration

Now you should be able to poll the required information from all RTUs within the UHF/VHF or cellular network.

[Note]Note

If you do not use the private APN, you need to configure the VPN tunnels. See VPN Configuration application note and SCADA Protocols public APN.

©  2024 RACOM s.r.o. All Rights Reserved.